APC Smart-UPS 5000VA 230V Rackmount/Tower
SUA5000RMI5U
APC Smart-UPS, 4000 Watts / 5000 VA,Input 230V / Output 230V, Rack Height 5 U
Includes: CD with software, Documentation CD, Installation guide, Rack mounting hardware, Rack Mounting support rails, Smart UPS signalling RS-232 cable, User Manual, Web/SNMP Management Card
Features
Adjustable voltage-transfer points
Boost and Trim Automatic Voltage Regulation (AVR)
Disconnected battery notification
Plug-and-Play installation
Resettable circuit breakers
Temperature-compensated battery charging
Output
Output Power Capacity
4000 Watts / 5000 VA
Max Configurable Power
4000 Watts / 5000 VA
Nominal Output Voltage
230V
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
Efficiency at Full Load
96.00%
Output Voltage Distortion
Less than 5% at full load
Output Frequency (sync to mains)
47 - 53 Hz for 50 Hz nominal
Output Connections
| (8) IEC 320 C13 |
|
| (2) IEC 320 C19 |
|
| (6) IEC Jumpers |
|
Input
Nominal Input Voltage
230V
Input Frequency
50/60 Hz +/- 3 Hz (auto sensing)
Input voltage range for main operations
160 - 286V
Input voltage adjustable range for mains operation
151 - 302V
Batteries & Runtime
Typical recharge time
3 hour(s)
Replacement battery cartridge
RBC55
Typical Backup Time
at Half Load
26.7 minutes (2000 Watts)
Typical Backup Time
at Full Load
9.4 minutes (4000 Watts)
Communications & Management
Pre-Installed SmartSlot™ Cards
AP9617
Control panel
LED status display with On Line : On Battery : Replace Battery and Overload indicators
Audible Alarm
Audible and visible alarms : configurable delays
Surge Protection and Filtering
Surge energy rating
480 Joules
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
Shipping Weight
106.82 KG
Shipping Height
635.00 mm
Environmental
Operating Environment
0 - 40 °C
Operating Relative Humidity
0 - 95%
Operating Elevation
0-9000 meters
Storage Temperature
-15 - 45 °C
Storage Relative Humidity
0 - 95%
Storage Elevation
0-15000 meters
Audible noise at 1 meter from surface of unit
53 dBA
Online Thermal Dissipation
430.00 BTU/hr
Conformance
Regulatory Approvals
C-tick,CE,EN 50091-1,EN 50091-2,GOST,GS Mark,VDE
Standard Warranty
2 years repair or replace
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS